Main Features
  • Unique IO design for local & remote IO
  • Universal input supports 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA, RTD
  • Thermistor
  • Analog output supports 0 ~ 10 V, 0 ~ 20 mA, and 4 ~ 20 mA (BAS-3024 only)
  • Supports PWM output (BAS-3024 only)
Datasheet (PDF) 3D model online view Download 3D Model Manual/ Driver/ BIOS/ FAQ
Introduction
BAS-3018/BAS-3024 expansion I/O modules can be stacked on the DDC controller, or can serve as remote standalone I/O modules through an RS-485 network. These expansion I/O modules add both scalability and flexibility to Advantech BAS-3000 solutions. Like the DDC, I/O expansion modules can be programmed using the BASPro programming tool.
Specifications
Part NumberBAS-3024-AE
Analog OutputChannels4
Resolution12-bit
Accuracy ± 0.1% of FSR
GeneralPower Input 24 VDC/24 VAC
Protection Isolation Voltage 3,000 VDC
Digital OutputChannels 4 (Source Type)
Vcc/Current10 ~ 35 VDC/1 A (per channel)
Universal InputChannels 44
Resolution16-bit
Accuracy ±0.1% of FSR (Voltage, Current)
Ordering Information
Part Number Description
  BAS-3024-AE 
RoHS
4-Ch UI, 4-ch AO, 4-ch DO Expansion Module
Contact Information
Office Phone Email
  Advantech U.S.A., Industrial Automation Group 1-800-205-7940 click to chat buy@advantech.com
  Advantech Headquarters, Industrial Automation Group 886-2-2218-4567 click to chat IA@advantech.com.tw
  Advantech Europe Customer Care Center, Industrial Automation Group 00-800-2426-8081 click to chat eAcustomercare@advantech.eu
Rate this page :
Did the information help you achieve your goal?
* Your eMail address:
Your Company
* Your Country:
Please provide us with comments to help improve this page:
Live Chat
Resources Download
eCatalog
Podcast
Whitepaper
Services
Featured Articles
Copyright © 1983-2010 Advantech Co., Ltd. All Rights Reserved RSS Site Map Privacy Policy
Country / Region [ Change ] | MyAdvantech |
Home Products Solutions Partners Support Contact Resources eStore
Search