MyAdvantechに登録

「MyAdvantech」はアドバンテックのお客様のための専用ポータルサイトです。メンバーに登録されたお客様には新製品、オンラインセミナー、eStoreでのディスカウントなどの情報を配信いたします。

メンバーに今すぐ登録!

Calculate the zero drift and span drift for temperature measuring.

2007-01-25 FAQ Document No.1-126357591

Related Product:

Solution:

  • Calculate the zero drift and span drift for temperature measuring.

    Description:
    For Analog Modules, the specs shows zero and span drift. In this document, the Adam-4011D is used an example to show how to calculate the value of drift.

    Solution:
    Temperature measurement errors can be caused by issues with Thermal couple accuracy, the accuracy of the AD converter, and/or the accuracy of CJC, as well as the zero drift and span drift. Setting aside the errors that can be caused by the thermal couple, AD converter and CJC, we focus on errors due to the zero drift and span drift.

    According to our specs of ADAM-4011D, zero drift is +/- 3 µV/ °C; span drift is +/-25 ppm/°C. Therefore if it is within the range of 80° C (-10 to 70° F), it might yield 288µV drift in total. 228 µV can be calculated as follows:
    Zero drift: 80° C* 3µV / µ = 240µ V.
    Span drift: 80° C* 25 ppm/ µ * 22mV = 44µ V

    22 mV is the voltage corresponding to T type TC table mapping to Max/min range (-100 ~ 400° C). It can be calculated as 20.872 mV (400° C) – –3.379mV (-100° C).
    Total drift = 240 + 44 = 284 µ V

    From T type TC table, 284 µV can be back mapped to the temperature of 8° C. According to our spec, the testing ambient temperature varying from -10~70° C will yield to 8° C due to the drift error. As a result, the error reading of +/- 4° C from our test should be reasonable and in the acceptable tolerance.

The content is too difficult to understand The content does not match the title The information is out of date It is not the information I'm looking for The content is empty Download file missing Invalid download link Download speed is slow Others

This field of information is requried

Yes No

This field of information is invalid

This field of information is requried

This field of information is requried

アドバンテックからのニュース(新製品、イベント情報など)を購読しますか?いつでも配信停止できます。*
アドバンテックからのニュース(新製品、イベント情報など)を購読しますか?いつでも配信停止できます。 は必須です*

ご注意: 「いいえ」 を選択すると、既に登録されている場合は現在の購読が解除されます。

アドバンテックのプライバシーポリシーに従って、個人情報を取り扱うことに同意しますか? *
アドバンテックのプライバシーポリシーに従って、個人情報を取り扱うことに同意しますか? は必須です*
전체동의 (선택사항 포함)

어드밴텍 이용약관 동의 전체보기*

This field of information is requried


개인정보 수집 및 이용 동의*

This field of information is requried


산업뉴스/적용사례/할인이벤트 이메일 수신 동의

당사는 회원 기반 서비스 제공을 위해 다음과 같이 개인정보를 수집하여 이용, 제공, 파기 합니다.

구분 수집항목 이용 목적 이용∙보유기간
1:1 문의 필수 이름, 이메일, 전화번호, 회사명, 국가, 상담내용 고객의 문의 대응 및 분쟁해결 등을 위함 소비자의 불만 또는 분쟁처리에 관한 기록: 3년
선택 제품, 시리얼넘버 효율적인 상담 대응
선택 뉴스레터 수신 동의 여부 신규 서비스/상품, 할인 이벤트 안내 법정 의무 보유 기간
I have read KVKK Clarification Text and I accept to share with you my personal data*

This field of information is requried


I have read KVKK Clarification Text for the Contact Form Process, I would like to receive Advantech emails and product information. Unsubscribe at any time. Already receiving Advantech Emails? Not ticking this box will automatically unsubscribe you
アドバンテックのプライバシーポリシーに基づき、売買手続き上必要な個人情報をアドバンテックが使用することに同意します。*

This field of information is requried


アドバンテックの製品情報、スペシャルオファー、重要なアドバンテックニュースの配信を希望します。(配信停止はいつでも可能です。)